There are six different seat leakage classifications as defined by ANSI FCI 70-2. The most commonly used by Gemco Valve are CLASS I, CLASS IV and CLASS Vl.
At a minimum, the requirements of Chapter 7 of NFPA 72, The National Fire Alarm Code, shall be followed. A preventive maintenance agreement should be arranged through the manufacturer’s local representative. Though smoke detectors are designed for long life, they may fail at any time. I've an FCI FC-72 FAP, and one of the two bell outs is failed. Only one leg (-) switches on alarm and supervision is gone, with the panel in trouble. There is a sparsly populated card (no relays or switches or IC's, only one transistor) in the signalling circuit expansion slot, with a lit trouble led on it.
CLASS I is also know as dust tight and can refer to metal or resilient seated valves.
- The FCI PS-6 is the primary power source for the FC-72 series fire alarm control. In addition to supplying the system with 4 amperes of filtered and regulated DC, the PS-6 contains a solid state battery charger which is capable of float charging sealed lead-acid batteries, or (optionally) charging nickel cadmium batteries.
- Fci zdm01 zone module for fc 72. What you see in picture is what you will receive. Customer satisfaction. 6 month customer satisfaction assurance program provided (replacement or refund) shipping. Free ups ground shipping. Payment accepted via paypal.
CLASS IV is also known as metal to metal. It is the kind of leakage rate you can expect from a valve with a metal shut-off disc and metal seat.
CLASS Vl is known as a soft seat classification. Soft Seat Valves are those where the seat or shut-off disc or both are made from some kind of resilient material such as Teflon.
Control Valve Seat Leakage Classifications – ANSI FCI 70-2 superseding ANSI B16.104
Leakage Class Designation | Maximum Leakage Allowable | Test Medium | Test Pressure | Testing Procedures Required for Establishing Rating |
---|---|---|---|---|
Class I | XXX | XXX | XXX | No test required provided user and supplier so agree |
Class II | 0.5% of rated capacity | Air or water at 50-125 F (10-52C) | 45-60 psig or max. operating differential whichever is lower | Pressure applied to valve inlet with outlet open to atmosphere or connected to a low head loss measuring device full normal closing thrust provided by actuator. |
Class III | 0.1% of rated capacity | Air or water at 50-125 F (10-52C) | 45-60 psig or max. operating differential whichever is lower | Pressure applied to valve inlet with outlet open to atmosphere or connected to a low head loss measuring device full normal closing thrust provided by actuator. |
Class IV | 0.01% of rated capacity | Air or water at 50-125 F (10-52C) | 45-60 psig or max. operating differential whichever is lower | Pressure applied to valve inlet with outlet open to atmosphere or connected to a low head loss measuring device full normal closing thrust provided by actuator. |
Class V | 0.0005 ml per minute of water per inch of port diameter per psi differential | Water at 50-125F (10-52C) | Max service pressure drop across valve plug, not to exceed ANSI body rating. | Pressure applied to valve inlet after filling entire body cavity and connected piping with water and stroking valve plug closed. Use net specified max actuator thrust, but no more, even if available during test. Allow time for leakage flow to stabilize. |
Class VI | Not to exceed amounts shown in following table based on port diameter. | Air or nitrogen at 50-125 F (10-52C) | 50 psig or max rated differential pressure across valve plug whichever is lower. | Actuator should be adjusted to operating conditions specified with full normal closing thrust applied to valve plug seat. Allow time for leakage flow to stabilize and use suitable measuring device. |
Fci 72 Battery Light On
NOMINAL PORT DIAMETER (Inches) | NOMINAL PORT DIAMETER (Millimeters) | LEAK RATE (ml per Minute) | LEAK RATE (Bubbles / minute*) |
---|---|---|---|
3 | 76 | 0.9 | 6 |
4 | 102 | 1.7 | 11 |
6 | 152 | 4 | 27 |
8 | 203 | 6.75 | 45 |
10 | 254 | 9 | 63 |
12 | 305 | 11.5 | 81 |
Fci 7200 Manual
*Bubbles per minute as tabulated are a suggested alternative based on a suitable calibrated measuring device, in this case a 0.25-inch OD X 0.032-inch wall tube submerged in water to a depth of from 1/8 to 1/4 inch. The tube end shall be cut square and smooth with no chamfers or burrs. The tube axis shall be perpendicular to the surface of the water. Other measuring devices may be constructed and the number of bubbles per minute may differ from those shown as long as they correctly indicate the flow in milliliters per minute.